The IEEE Reliability Test System (IEEE-RTS) ------------------------------------------- I. Load data: -------------- Annual peak load: 2850 MW Table 1: Weekly peak load in percent of annual peak --------------------------------------------------- W: Week PL: Peak load in percent of annual peak (W) (PL) (W) (PL) (W) (PL) (W) (PL) 1 86.2 14 75.0 27 75.5 40 72.4 2 90.0 15 72.1 28 81.6 41 74.3 3 87.8 16 80.0 29 80.1 42 74.4 4 83.4 17 75.4 30 88.0 43 80.0 5 88.0 18 83.7 31 72.2 44 88.1 6 84.1 19 87.0 32 77.6 45 88.5 7 83.2 20 88.0 33 80.0 46 90.9 8 80.6 21 85.6 34 72.9 47 94.0 9 74.0 22 81.1 35 72.6 48 89.0 10 73.7 23 90.0 36 70.5 49 94.2 11 71.5 24 88.7 37 78.0 50 97.0 12 72.7 25 89.6 38 69.5 51 100.0 13 70.4 26 86.1 39 72.4 52 95.2 Table 2: Daily peak load in percent of weekly peak -------------------------------------------------- PL: Peak load in percent of weekly peak (Day) (PL) Monday 93 Tuesday 100 Wednesday 98 Thursday 96 Friday 94 Saturday 77 Sunday 75 Table 3: Hourly peak load in percent of daily peak -------------------------------------------------- Winter: Winter weeks (1-8 and 44-52) Summer: Summer weeks (18-30) Sprint/Fall: Spring and Fall weeks (9-17 and 31-43) Wd: Week day load in percent of daily peak We: Week end load in percent of daily peak [Winter] [Summer] [Spring/Fall] (Hour) (Wd) (We) (Wd) (We) (Wd) (We) 12-1 am 67 78 64 74 63 75 1-2 63 72 60 70 62 73 2-3 60 68 58 66 60 69 3-4 59 66 56 65 58 66 4-5 59 64 56 64 59 65 5-6 60 65 58 62 65 65 6-7 74 66 64 62 72 68 7-8 86 70 76 66 85 74 8-9 95 80 87 81 95 83 9-10 96 88 95 86 99 89 10-11 96 90 99 91 100 92 11-Noon 95 91 100 93 99 94 Noon-1 pm 95 90 99 93 93 91 1-2 95 88 100 92 92 90 2-3 93 87 100 91 90 90 3-4 94 87 97 91 88 86 4-5 99 91 96 92 90 85 5-6 100 100 96 94 92 88 6-7 100 99 93 95 96 92 7-8 96 97 92 95 98 100 8-9 91 94 92 100 96 97 9-10 83 92 93 93 90 95 10-11 73 87 87 88 80 90 11-12 63 81 72 80 70 85 II. Generation System data: --------------------------- Type: Type of generating units Cap: Capacity of each unit (MW) N: Number of units MTTF: Mean time to failure (hours) MTTR: Mean time to repair (hours) (Type) (Cap) (N) (MTTF) (MTTR) Oil 12 5 2940 60 Oil 20 4 450 50 Hydro 50 6 1980 20 Coal 76 4 1960 40 Oil 100 3 1200 50 Coal 155 4 960 40 Oil 197 3 950 50 Coal 350 1 1150 100 Nuclear 400 2 1100 150 Reference: ---------- IEEE Commmitte Report, "IEEE Reliability Test System", IEEE Transactions on Power Apparatus and Systems, Vol. PAS-98, No. 6, pp. 2047-2054, Nov/Dec 1979.